Checking the Earth Leakage Breaker

This section explains how to check the earth leakage breaker.

WARNING


  • When this machine's circuit breaker is set to "Off", do not switch it to "On". Doing so could result in electric shock, fire, smoke, or tripping of the room's breakers.

Important

This machine has two earth leakage breakers.

For details about where they are located, see "Guide to Components", About This Machine.

Some options are equipped with earth leakage breakers.

Once a year, check that the earth leakage breakers function properly. Normally, the breakers are in the On position.

Check both breakers in the same way.

  1. Press the operation switch to turn off the power.

  2. Turn off the main power.

  3. Using a ballpoint pen or similar pointed object, press in the earth leakage breaker's test button.

    Earth leakage breaker illustration

  4. Check that the earth leakage breaker moves to the Off position.

    Earth leakage breaker illustration

  5. Return the earth leakage breaker to the On position.

    Earth leakage breaker illustration

  6. Turn on the main power.